"FLOWLINK" Shell & Tube Direct Expansion Refrigeration Chillers are designed and fabricated under the direct supervision of a team of Engineers well experienced in the line of Heat Transfer Equipment. Every care is taken to ensure a long and trouble free service and the desired performance from the equipment.

TYPES :-
- Fixed Tube Sheet typr horizontal Chillers ·
- Removable "U" Tube type Chillers
DESIGN :-
Our experienced design engineers are always at service to design for you the most economical chillers for the specific cooling application. Proper selection and sizing of the chiller best suited for your needs is of utmost importance for achieving the desired results in operation.

DATA REQUIRED FOR DESIGN :-
Fluid to be cooled (Incase of Aqueous solutions, specify concentration)
System Refrigerant (F-22 / F-12 / Ammonia)
Design Refrigerant Evap. Temp (°C)
Fluid Flow Rate (LPM)
Fluid inlet Temp. (°C)
Fluid outlet Temp. (°C)
Refrigeration Load (K Cal/ Hr)

In case of unusual fluids, its properties like Sp. Gravity, Viscosity & Thermal Conductivity should be given.

SPECIFICATION
SHELL : Electrically welded steel pipes confirming to IS-3589 or Eq.
TUBES : Standard D.X. chillers, for use as water chillers with Freons (12 or 22) as refrigerant, are fabricated with seamless solid drawn plain copper tubes.

For cooling Brines of other liquids, different tube material may have to be used depending upon the characteristics of the liquid to be cooled. For Ammonia as refrigerant, ERW steel tubes confirming to BS-3059/4 / Eq. are standard. Seamless steel tubes confirming to SA-179 / Eq. can be offered in specific cases.

TUBE SHEETS : Mild Steel IS-2062 / Eq.
HEADS : Mild Steel formed Dished ends welded to heavy duty flanges.
TUBE TO TUBE SHEET
JOINT : Roller Expanded with automatic electronic expanding machines to give uniform and leak free joints.
SHELL SIDE TUBE SIDE
FLUID Liquid to be cooled Refrigerant
DESIGN PRESSURE 6 20 Kg/Cm Sq at 100°C Kg/Cm Sq. at 100°C
TEST PRESSURE 30 Kg/Cm Sq. 10 Kg/ Cm Sq.